<?xml version="1.0" encoding="utf-8"?>
<!DOCTYPE document PUBLIC "-//CNX//DTD CNXML 0.5//EN" "http://cnx.rice.edu/technology/cnxml/schema/dtd/0.5/cnxml_plain.dtd">
<document xmlns="http://cnx.rice.edu/cnxml" xmlns:md="http://cnx.rice.edu/mdml/0.4" xmlns:bib="http://bibtexml.sf.net/" id="id14498466">
<name>Control Lab Setup: Using LabVIEW to Control ECP Plants</name>
<metadata>
  <md:version>1.4</md:version>
  <md:created>2005/10/18 15:24:53 GMT-5</md:created>
  <md:revised>2006/07/21 18:42:13.050 GMT-5</md:revised>
  <md:authorlist>
      <md:author id="Robert_Bishop">
      <md:firstname>Robert</md:firstname>
      
      <md:surname>Bishop</md:surname>
      <md:email>rhbishop@mail.utexas.edu</md:email>
    </md:author>
      <md:author id="nicklin">
      <md:firstname>Nick</md:firstname>
      <md:othername>H</md:othername>
      <md:surname>Lin</md:surname>
      <md:email>nicklin@mail.utexas.edu</md:email>
    </md:author>
  </md:authorlist>

  <md:maintainerlist>
    <md:maintainer id="Robert_Bishop">
      <md:firstname>Robert</md:firstname>
      
      <md:surname>Bishop</md:surname>
      <md:email>rhbishop@mail.utexas.edu</md:email>
    </md:maintainer>
    <md:maintainer id="nicklin">
      <md:firstname>Nick</md:firstname>
      <md:othername>H</md:othername>
      <md:surname>Lin</md:surname>
      <md:email>nicklin@mail.utexas.edu</md:email>
    </md:maintainer>
    <md:maintainer id="eluther">
      <md:firstname>Erik</md:firstname>
      <md:othername>B</md:othername>
      <md:surname>Luther</md:surname>
      <md:email>erik.luther@ni.com</md:email>
    </md:maintainer>
  </md:maintainerlist>
  
  

  <md:abstract>This document describes the specifics users will experience when controlling an ECP plant with LabVIEW with front panel and block diagram screen shots.  Much thought has been put in to creating a set of example VIs that will work for each plant in their standard configuration as well as with the pendulum accessory.  I/O is also explained in detail, including scaling units used for encoder input and analog output.</md:abstract>
</metadata>
<content>
<section id="id14685362">
<name>Using LabVIEW to Control ECP Plants</name>
<para id="id14591715">This document provides a brief overview of
how to use the National Instruments LabVIEW Virtual Instrument (VI)
developed by The University of Texas at Austin Aerospace
Engineering Controls Laboratory to perform control system
experiments with the Educational Control Products (ECP) Model 210
Rectilinear and Model 205 Torsional plants.</para>
<section id="id14685306">
<name>FPGA Personality VIs:</name>
<section id="id14685312">
<name>FPGA VI Specifics for each Plant</name>
<para id="id14627601">The provided FPGA VIs contain the code for
the reconfigurable I/O board which sends and receives signals, such
as motor drive voltage and quadrature encoder channels, from the
plants. Furthermore, the FPGA code incorporates safety features,
such as motor overvoltage protection, to help prevent damage to the
plants.</para>
<para id="id14442471">The FPGA VIs for the two plants are similar
but differ in the following ways:
<list type="enumerated" id="id14442480">
<item>For the Model 205 Torsional Plant, the A and B channels for
encoder 3 have been switched due to the fact that the physical
orientation of encoder 3 is opposite that of encoders 1 and
2.</item>
<item>The Model 205 Torsional Plant does not have limit switches,
but to prevent damage to the torsion rods, the VI will write zero
voltage to the drive motor in the event that the displacement
between disks 1 and 2 or disks 2 and 3 exceeds 3000 counts (67.5
degrees). The voltage will remain at zero until the error is
cleared.

<list type="bulleted" id="id14689720"><item>File Name of LabVIEW 8.0 Project: ECP 205 Project.lvproj (within LabVIEW 8.0 Starting Point.zip below)</item>
<item>File Name of LabVIEW 7.1 Project: ECP 205.lep (within LabVIEW 7.1 Starting Point.zip below)</item>
</list>
</item>

<item>The Model 210 Rectilinear Plant has limit switches to prevent
damage due to excessive travel of the mass carriages. If a limit
switch is engaged, the VI returns a value of true to an error
indicator and writes zero voltage to the drive motor until the
error is cleared.

<list type="bulleted" id="id14625627"><item>File Name of LabVIEW 8.0 Project: ECP 210 Project.lvproj (within LabVIEW 8.0 Starting Point.zip below)</item>
<item>File Name of LabVIEW 7.1 Project: ECP 210.lep (within LabVIEW 7.1 Starting Point.zip below)</item></list>
</item>
</list>
</para>
<note> The FPGA personality can be dowloaded with example programs below under <cnxn target="id14617772">Starting-Point VI’s for Each Plant</cnxn>. </note><para id="id14625650">The FPGA VI for both plants incorporates
drive motor overvoltage protection. If an overvoltage condition is
detected, zero voltage will be written to the motor until the error
is cleared.</para>
<para id="id14626469">The portion of the code which interprets
encoder signals has been written such that for the 210 plant, a
displacement to the right results in a positive measurement. For
the 205 plant, a positive measurement results from a
counterclockwise disk displacement. When using the ECP pendulum
accessory, a counterclockwise rotation will result in a positive
encoder measurement (encoder 4).</para>
<para id="id14626488">The portion of the code which sends signals
to the drive motor has been written such that a positive control
effort results in a counterclockwise (when viewed from the shaft)
rotation of the drive motor. Therefore, for the 210 plant, this
will result in an input force to the right. For the 205 plant, this
will result in a clockwise input torque at the base disk.</para>
<para id="id14481965">If you decide to write new FPGA code using
the LabVIEW Embedded Project Manager, use the following tables as a
reference for assigning FPGA channels:</para>

<list type="bulleted" id="id14443054">
<item>Note that if you use the ECP pendulum accessory and are
required to connect the pendulum encoder cable manually to the
terminal block inside the amplifier box, then you should connect
the +5V and ground wire to pins 2 and 4, respectively, on the
terminal block. This is due to the fact that the National
Instruments ECP to RIO cable maps the +5V and ground channels for
all the encoders to only pins 2 and 4 on the terminal block. ECP
may instruct you to connect the +5V and ground wires for encoder 4
to pins 1 and 3 on the terminal block; however, doing so will
result in the encoder not receiving power.</item>
<item><emphasis>Encoder Counts Per Revolution</emphasis>
<list type="bulleted" id="id14728561">
<item>Encoder 1: 16000 counts = 360 degrees</item>
<item>Encoder 2: 16000 counts = 360 degrees</item>
<item>Encoder 3: 16000 counts = 360 degrees</item>
<item>Encoder 4: 16384 counts = 360 degrees (pendulum encoder)
**</item>
</list></item>
</list>
<note>See <cnxn target="id14443054">special hook-up instructions</cnxn> for the pendulum encoder on note above.  This only applies to the ECP pendulum attachment that requires bare wires to be hooked up inside the ECP Amplifier box.</note>
</section>
<section id="id14644554">
<name>Autorunning FPGA VIs to Zero Analog Outputs:</name>
<note> This must only be done once for the life of the FPGA Board.</note>
<para id="id14644570">To ensure that the system has the correct
power on states when the real-time target is booted but before the
control loop VI is run, you should configure the target to autorun
the FPGA VI at power on. To enable this feature, the “Autorun VI”
option should be selected when building the FPGA project code.
Then, in the LabVIEW Embedded Project Manager, select Tools
&gt;&gt; Download VI or Attributes to Flash Memory. In this window,
you can download the FPGA VI from the host machine to the flash
memory on the target and configure autoload options. See Chapter 4
of the LabVIEW FPGA Module User’s Manual for more
information.</para>
</section>
</section>
<section id="id14617764">
<name>Using the Real-Time VI for Control System Experiments</name>
<section id="id14617772">
<name>Starting-Point VI’s for Each Plant</name>
<list type="bulleted" id="element-538"><item>LabVIEW Real Time for ETS Example VIs
<list type="bulleted" id="element-540"><item>ECP 205 and 210 LabVIEW 8.0 Project: <link src="ECP_LabVIEW_8.0_Starting_Point.zip"> ECP_LabVIEW_8.0_Starting_Point.zip (download)</link> - FPGA personality included</item>

<item>ECP 205 and 210 LabVIEW 7.1 Project: <link src="ECP_LabVIEW_7.1_Starting_Point.zip"> ECP_LabVIEW_7.1_Starting_Point.zip (download)</link> - FPGA personality included</item>
</list></item>
<item>LabVIEW Real Time for RTX Example VIs
<list type="bulleted" id="element-545"><item>ECP 210 Rectilinear Plant: not yet posted </item>
<item>ECP 205 Torsional Plant: not yet posted </item>
</list></item></list>

<para id="id14626972"/>
</section>
<section id="id14626978">
<name>Usage Instructions</name>
<para id="id14626985">Extract all folders and VIs to a directory on
your host PC. Be sure to keep the file and folder paths intact to
avoid having to relocate VIs. The files in the FPGA VIs and Sub VIs
folders do not need to be changed. Target your real-time device
from the LabVIEW start-up screen and then open the example ECP 210
1DOF PID.vi. You will see the front panel shown below:</para>
<figure id="id14627011">
<media type="image/jpg" src="Graphic1"/>

<caption>LabVIEW front panel of example <cnxn target="id14617772">ECP 210 1DOF PID.vi</cnxn></caption></figure>
<para id="id14229263">Take a few moments to familiarize yourself
with the various controls and indicators that are available on the
front panel.</para>
<para id="id14229273">When you are ready, power on the ECP
amplifier box and run the VI. Once the VI completes downloading to
the PXI, the closed-loop system is active (or open-loop in the case
of no controller). In this example, a PID controller is being used
to control the position of a 1DOF rigid-body system. The first mass
cart on the ECP Model 210 plant is loaded with four 0.5kg weights
and no springs or dashpots are attached.</para>
<figure id="id14229294">
<media type="image/png" src="Graphic2"/>

<caption>Partial shot of the ECP Model 210 Plant</caption></figure>
<para id="id14627632">You may apply a light external force to the
mass cart and feel the controller respond by attempting to
attenuate the disturbance. Also, notice that encoder position
measurements are displayed on the front panel. Pressing the Reset
Encoders control will set all the encoders back to 0.</para>
<para id="id14627649">If any of the error conditions are detected
(limit switches, drive motor overvoltage, etc), the VI will perform
a safety shutdown and you will need to re-run it.</para>
<para id="id14627656">If you wish to command a test signal to the
system, press the Command Trajectory control. The Sub VI front
panel shown below will pop open:</para>
<figure id="id14627672">
<media type="image/jpg" src="Graphic3"/>

<caption>Command tragjectory interface</caption></figure>
<note> The <emphasis>Test Signals</emphasis> feature is only available when using LabVIEW Real-Time for ETS, because of the additional overhead required for the interactive user interface.</note><para id="id14362549">Take a moment to tab through the various
types of test signals that are available as well as what parameters
you may prescribe for each signal. Selecting the bidirectional
inputs option causes the commanded signal to alternate directions
when more than one repetition is specified. You may always press
the Preview Trajectory control to see a preview of the signal. When
you are satisfied with your selection, press the Execute Trajectory
control. The Sub VIs front panel will close and the signal will be
sent to the system as the reference trajectory that is to be
tracked.</para>
<para id="id14362576">When the trajectory is complete, plot data
will be calculated. This may take a few seconds depending on the
duration of your specified trajectory. When the data calculation
completes you may toggle on and off any trajectories that you wish
to view on the graph indicator such as position, velocity, and
acceleration. Note that the velocity and acceleration amplitudes
have been scaled by 0.1 and 0.01, respectively, on the
graph.</para>
<para id="id14362598">Try using the graph indicator’s zoom options
if you wish to zoom in on a portion of the graph.</para>
<para id="id14362609">Toggling the cursor on brings up the cursor
on the graph. You may lock the cursor to any of the 14 plot
histories and click and drag on it to obtain point-by-point numeric
data. The first number shown in the cursor legend is the time and
the second is the amplitude for the plot to which you are currently
locked.</para>
<para id="id14362626">If you wish to save the data, enter a file
name in the path control on the front panel and press the Save Raw
Data control. This will save the time, reference signal, control
effort, and four encoder position histories for the commanded
trajectory; velocity and acceleration data are not saved. The file
is saved as spreadsheet data on the PXI’s hard drive. You may use
an FTP client of your choice to access the PXI and copy the file to
your host machine.</para>
<para id="id14626138">When you are finished with your experiment,
press the Abort Control control on the front panel and the VI will
shut down the control loop.</para>
<para id="id14626145"><emphasis>Programming a Control Algorithm in the VI’s
Block Diagram:</emphasis></para>
<para id="id14626155">The Real-Time control loop VI has been
written such that a variety of control algorithms can be
implemented with little change to the VI’s block diagram code. The
only change that needs to be made is the code that exists between
the reference signal (desired position) and the control effort
(analog output).</para>
<para id="id14626173">Open the block diagram for the VI (shown
below) to see how the PID controller for this example was
implemented:</para>
<figure id="id14626186">
<media type="image/jpg" src="Graphic4"/>

<caption>Partial block diagram view of Example VI <cnxn target="id14617772">ECP 210 1DOF PID.vi</cnxn></caption></figure>
<para id="id14626213">The encoder measurement is subtracted from
the reference signal to generate the error signal, which is sent
through the PID algorithm. Finally, the control effort signal
calculated by the PID is sent to the analog output channel that
drives the plant motor.</para>
<para id="id14626227">It can be seen that programming other
controllers such as phase lead, LQR, etc could be easily
accomplished by deleting the current algorithm and coding a new one
in its place.</para>
<para id="id14531221">To perform experiments for the open-loop case
(useful when studying the system’s natural dynamics or when
performing system identification), you may simply delete the
feedback control algorithm and connect the reference trajectory
point directly to the analog output. Recall that the analog output
channels on the reconfigurable I/O board have a range of +10V to
-10V and a 16-bit DAC resolution. Therefore, in the open-loop case,
a command signal amplitude of -32768 to +32767 corresponds to -10V
to +10V sent to the drive motor.</para>
<para id="id14531243">Please refer to the following resources for
more detailed plant dynamics and hardware descriptions:</para>
<para id="id14531253">ECP Plant Manuals and National Instruments Resources: </para>
<list type="bulleted" id="element-267"><item>Manual for Model 210/210a Rectilinear Control System (Instructor’s Edition)</item>
<item>Manual for Model 205/205a Torsional Control System (Instructor’s Edition)</item>
<item>National Instruments PCI/PXI 7831R Hardware: <link src="http://www.ni.com/pdf/manuals/370489b.pdf">
http://www.ni.com/pdf/manuals/370489b.pdf</link></item>
<item>Additional NI hardware and LabVIEW programming resources can be found on <link src="http://www.ni.com/">
http://www.ni.com/</link></item></list>




</section>
</section>
</section>
</content>
</document>