PROBLEMS
This lecture note is based on the textbook # 1. Electric Machinery - A.E. Fitzgerald, Charles Kingsley, Jr., Stephen D. Umans- 6th edition- Mc Graw Hill series in Electrical Engineering. Power and Energy
2.1 A transformer is made up of a 1200-turn primary coil and an open-circuited 75-turn secondary coil wound around a closed core of cross-sectional area 42
2.2 A magnetic circuit with a cross-sectional area of 15
2.3 A transformer is to be used to transform the impedance of a 8
2.4 A 100
2.5 A source which can be represented by a voltage source of 8 V rms in series with an internal resistance of 2
2.6 Repeat Problem 2.5 with the source resistance replaced by a 2-
2.7 A single-phase 60-Hz transformer has a nameplate voltage rating of 7.97 kV:266 V, which is based on its winding turns ratio. The manufacturer calculates that the primary (7.97-kV) leakage inductance is 165 mH and the primary magnetizing inductance is 135 H. For an applied primary voltage of 7970 V at 60 Hz, calculate the resultant open-circuit secondary voltage.
2.8 The manufacturer calculates that the transformer of Problem 2.7 has a secondary leakage inductance of 0.225 mH.
a. Calculate the magnetizing inductance as referred to the secondary side.
b. A voltage of 266 V, 60 Hz is applied to the secondary. Calculate (i) the resultant open-circuit primary voltage and (ii) the secondary current which would result if the primary were short-circuited.
2.9 A 120-V:2400-V, 60-Hz, 50-kVA transformer has a magnetizing reactance (as measured from the 120-V terminals) of 34.6
a. With the secondary open-circuited and 120 V applied to the primary (120-V) winding, calculate the primary current and the secondary voltage.
b. With the secondary short-circuited, calculate the primary voltage which will result in rated current in the primary winding. Calculate the corresponding current in the secondary winding.
2.10 A 460-V:2400-V transformer has a series leakage reactance of 37.2
2.11 The resistances and leakage reactances of a 30-kVA, 60-Hz, 2400-V:240-V distribution transformer are
R1 = 0.68
where subscript 1 denotes the 2400-V winding and subscript 2 denotes the 240-V winding. Each quantity is referred to its own side of the transformer.
a. Draw the equivalent circuit referred to (i) the high- and (ii) the low-voltage sides. Label the impedances numerically.
b. Consider the transformer to deliver its rated kVA to a load on the low-voltage side with 230 V across the load. (i) Find the high-side terminal voltage for a load power factor of 0.85 power factor lagging. (ii) Find the high-side terminal voltage for a load power factor of 0.85 power factor leading.
c. Consider a rated-kVA load connected at the low-voltage terminals operating at 240V. Use MATLAB to plot the high-side terminal voltage as a function of the power-factor angle as the load power factor varies from 0.6 leading through unity power factor to 0.6 pf lagging.
2.12 Repeat Problem 2.11 for a 75-kVA, 60-Hz, 4600-V:240-V distribution transformer whose resistances and leakage reactances are
R1 = 0.846
where subscript 1 denotes the 4600-V winding and subscript 2 denotes the 240-V winding. Each quantity is referred to its own side of the transformer.
2.13 A single-phase load is supplied through a 35-kV feeder whose impedance is 95+j360
a. Compute the voltage at the high-voltage terminals of the transformer.
b. Compute the voltage at the sending end of the feeder.
c. Compute the power and reactive power input at the sending end of the feeder.
2.14 The nameplate on a 50-MVA, 60-Hz single-phase transformer indicates that it has a voltage rating of 8.0-kV:78-kV. An open-circuit test is conducted from the low-voltage side, and the corresponding instrument readings are 8.0 kV, 62.1 A, and 206 kW. Similarly, a short-circuit test from the low-voltage side gives readings of 674 V, 6.25 kA, and 187 kW.
a. Calculate the equivalent series impedance, resistance, and reactance of the transformer as referred to the low-voltage terminals.
b. Calculate the equivalent series impedance of the transformer as referred to the high-voltage terminals.
c. Making appropriate approximations, draw a T equivalent circuit for the transformer.
d. Determine the efficiency and voltage regulation if the transformer is operating at the rated voltage and load (unity power factor).
e. Repeat part (d), assuming the load to be at 0.9 power factor leading.
2.15 A 550-kVA, 60-Hz transformer with a 13.8-kV primary winding draws 4.93 A and 3420 W at no load, rated voltage and frequency. Another transformer has a core with all its linear dimensions
2.16 The following data were obtained for a 20-kVA, 60-Hz, 2400:240-V distribution transformer tested at 60 Hz:
![]() |
a. Compute the efficiency at full-load current and the rated terminal voltage at 0.8 power factor.
b. Assume that the load power factor is varied while the load current and secondary terminal voltage are held constant. Use a phasor diagram to determine the load power factor for which the regulation is greatest. What is this regulation?
2.17 A 75-kVa, 240-V:7970-V, 60-Hz single-phase distribution transformer has the following parameters referred to the high-voltage side:
R1 = 5.93
R2 = 3.39
Rc = 244
Assume that the transformer is supplying its rated kVA at its low-voltage terminals. Write a MATLAB script to determine the efficiency and regulation of the transformer for any specified load power factor (leading or lagging). You may use reasonable engineering approximations to simplify your analysis. Use your MATLAB script to determine the efficiency and regulation for a load power factor of 0.87 leading.
2.18 The transformer of Problem 2.11 is to be connected as an autotransformer. Determine (a) the voltage ratings of the high- and low-voltage windings for this connection and (b) the kVA rating of the autotransformer connection.
2.19 A 120:480-V, 10-kVA transformer is to be used as an autotransformer to supply a 480-V circuit from a 600-V source. When it is tested as a two-winding transformer at rated load, unity power factor, its efficiency is 0.979.
a. Make a diagram of connections as an autotransformer.
b. Determine its kVA rating as an autotransformer.
c. Find its efficiency as an autotransformer at full load, with 0.85 power factor lagging.
2.20 Consider the 8-kV:78-kV, 50-MVA transformer of Problem 2.14 connected as an autotransformer.
a. Determine the voltage ratings of the high- and low-voltage windings for this connection and the kVA rating of the autotransformer connection.
b. Calculate the efficiency of the transformer in this connection when it is supplying its rated load at unity power factor.
2.21 Write a MATLAB script whose inputs are the rating (voltage and kVA) and rated-load, unity-power-factor efficiency of a single-transformer and whose output is the transformer rating and rated-load, unity-power-factor efficiency when connected as an autotransformer.
2.22 The high-voltage terminals of a three-phase bank of three single-phase transformers are supplied from a three-wire, three-phase 13.8-kV (line-to-line) system. The low-voltage terminals are to be connected to a three-wire, three-phase substation load drawing up to 4500kVA at 2300 V line-to-line. Specify the required voltage, current, and kVA ratings of each transformer (both high- and low-voltage windings) for the following connections:
![]() |
2.23 Three 100-MVA single-phase transformers, rated at 13.8 kV:66.4 kV, are to be connected in a three-phase bank. Each transformer has a series impedance of 0.0045 + j0.19
a. If the transformers are connected Y-Y, calculate (i) the voltage and power rating of the three-phase connection, (ii) the equivalent impedance as referred to its low-voltage terminals, and (iii) the equivalent impedance as referred to its high-voltage terminals.
b. Repeat part (a) if the transformer is connected Y on its low-voltage side and
2.24 A three-phase
2.25 Assume the total load in the system of Problem 2.24 to remain constant at 325 MVA. Write a MATLAB script to plot the line-to-line voltage which must be applied to the sending end of the feeder to maintain the load voltage at 24 kV line-to-line for load power factors in range from 0.75 lagging to unity to 0.75 leading. Plot the sending-end voltage as a function of power factor angle.
2.26 A Δ-Y-connected bank of three identical 100-kVA, 2400-V:120-V, 60-Hz transformers is supplied with power through a feeder whose impedance is 0.065 + j0.87
VH=53.4V f=60Hz IH=41.7A P=832W
a. Determine the line-to-line voltage on the low-voltage side of the transformer when the bank delivers rated current to a balanced three-phase unity power factor load.
b. Compute the currents in the transformer's high- and low-voltage windings and in the feeder wires if a solid three-phase short circuit occurs at the secondary line terminals.
2.27 A 7970-V: 120-V, 60-Hz potential transformer has the following parameters as seen from the high-voltage (primary) winding:
X1 = 1721
R1 = 1378
a. Assuming that the secondary is open-circuited and that the primary is connected to a 7.97-kV source, calculate the magnitude and phase angle (with respect to the high-voltage source) of the voltage at the secondary terminals.
b. Calculate the magnitude and phase angle of the secondary voltage if a 1
c. Repeat part (b) if the burden is changed to a 1 ***SORRY, THIS MEDIA TYPE IS NOT SUPPORTED.*** reactance.
2.28For the potential transformer of Problem 2.27, find the maximum reactive burden (mimimum reactance) which can be applied at the secondary terminals such that the voltage magnitude error does not exceed 0.5 percent.
2.29Consider the potential transformer of Problem 2.27.
a. Use MATLAB to plot the percentage error in voltage magnitude as a function of the magnitude of the burden impedance (i) for a resistive burden of 100
b. Next plot the phase error in degrees as a function of the magnitude of the burden impedance (i) for a resistive burden of 100
2.30 A 200-A:5-A, 60-Hz current transformer has the following parameters as seen from the 200-A (primary) winding:
X1 = 745
R1 = 136
a. Assuming a current of 200 A in the primary and that the secondary is short-circuited, find the magnitude and phase angle of the secondary current.
b. Repeat the calculation of part (a) if the CT is shorted through a 250
2.31 Consider the current transformer of Problem 2.30.
a. Use MATLAB to plot the percentage error in current magnitude as a function of the magnitude of the burden impedance (i) for a resistive burden of 100
b. Next plot the phase error in degrees as a function of the magnitude of the burden impedance (i) for a resistive burden of
2.32 A 15-kV: 175-kV, 125-MVA, 60-Hz single-phase transformer has primary and secondary impedances of 0.0095 + j0.063 per unit each. The magnetizing impedance is j148 per unit. All quantities are in per unit on the transformer base. Calculate the primary and secondary resistances and reactances and the magnetizing inductance (referred to the low-voltage side) in ohms and henrys.
2.33 The nameplate on a 7.97-kV:460-V, 75-kVA, single-phase transformer indicates that it has a series reactance of 12 percent (0.12 per unit).
a. Calculate the series reactance in ohms as referred to (i) the low-voltage terminal and (ii) the high-voltage terminal.
b. If three of these transformers are connected in a three-phase Y-Y connection, calculate (i) the three-phase voltage and power rating, (ii) the per unit impedance of the transformer bank, (iii) the series reactance in ohms as referred to the high-voltage terminal, and (iv) the series reactance in ohms as referred to the low-voltage terminal.
c. Repeat part (b) if the three transformers are connected in Y on their HV
side and
2.34 a. Consider the Y-Y transformer connection of Problem 2.33, part (b). If the rated voltage is applied to the high-voltage terminals and the three low-voltage terminals are short-circuited, calculate the magnitude of the phase current in per unit and in amperes on (i) the high-voltage side and (ii) the low-voltage side.
b. Repeat this calculation for the Y-
2.35 A three-phase generator step-up transformer is rated 26-kV:345-kV, 850 MVA and has a series impedance of 0.0035 + j0.087 per unit on this base. It is connected to a 26-kV, 800-MVA generator, which can be represented as a voltage source in series with a reactance of j1.57 per unit on the generator base.
a. Convert the per unit generator reactance to the step-up transformer base.
b. The unit is supplying 700 MW at 345 kV and 0.95 power factor lagging to the system at the transformer high-voltage terminals. (i) Calculate the transformer low-side voltage and the generator internal voltage behind its reactance in kV. (ii) Find the generator output power in MW and the power factor.